The devices can set switch outputs,AC curtain outputs,DC curtain output,fan control output and valve control output. The output requirements are configured via parameter.
- Switch output: connect some electrical loads, such as lighting, sockets. All channels have the function of general switch, staircase lighting, light flashing and switch delay, scene,operation hours counter, logic and force operation;
- Curtain output(AC/DC): connect with motor blinds, awnings, roller blinds, vertical blind, etc. With operating shutter and slat adjustment, automatic sun protection , scene and safety operating etc.;
- Fan control: support up to three level fan speed, with general operation, forced operation, Auto. operation and status response etc.;
- Valve control: connect with 2pipes or 4pipes system, support three valve control types: 3point,open and close, continuous,PWM and 2state-ON/OFF, and support disable/enable HEAT and COOL, valve status response, valve purge etc..
- Heating control:support continuous,PWM and 2 state-ON/OFF,monitor and force function available
-
ModeAMMA-08/10.1
-
Dimension72 mm×90mm×64mm
-
InstallationDIN rail
-
Bus voltage21-30V DC, Via KNX bus
-
Bus current<12mA
-
Bus consumption<360mW
-
Capacitor charge current<20mA
-
Un rated voltage230V AC(50/60Hz), 30V DC
-
In rated current capacity10A/70uF (max.100W, if LED load)
-
Max. switching current16A/240V AC